Fault Managed Power Transmitter

The Clearfield Fault Managed Power Transmitter provides the centralized power and control for a Clearfield Fault Managed Power system. Paired with a compatible FMP receiver, it continuously monitors the circuit between the transmitter and the remote load. If it detects cable damage, a short circuit, contact with an exposed conductor, or another fault condition, it rapidly shuts down the affected output to help protect people, equipment, and infrastructure.

As part of a listed Class 4 system installed in accordance with NFPA 70 Article 726, Fault Managed Power can simplify the delivery of power to remote equipment. Power and fiber can follow a coordinated pathway, reducing the need for conventional AC or DC power infrastructure at the remote location and helping streamline installation, turn-up, and ongoing management.

Each 1U transmitter shelf supports up to two hot-swappable 3 kW power modules and four independently monitored output channels. A fully populated shelf delivers up to 6 kW, with transmission distances of up to 6,000 feet to compatible receivers. It is ideal for remote OLT and DAA nodes, small cells, wireless backhaul, edge compute, IoT enclosures, and other locations where utility power is costly, slow to provision, or unavailable.

Ask a Question

How Can We Help?

Product Details

One shelf, up to 6 kW, four supervised outputs

The transmitter chassis is a 1U, 19″/23″-rack-mountable shelf that accepts up to two hot-swappable power modules. A single module delivers up to 3 kW; populate both bays and the shelf delivers up to 6 kW — full-power operation on either configuration requires an input of 208 VAC or greater. Power modules can be pulled and replaced in service, without dropping the other channels on the shelf.

Each shelf exposes four independent Fault Managed Power output channels, each capable of up to 4.68 A, wired with field-terminated 18–12 AWG copper conductors through a pluggable, tool-less connector. Output reaches up to 6,000 ft over cable rated to 40 pF/ft, giving designers real routing flexibility between the equipment room and the remote load.

  • Rack fit: 19″ / 23″ EIA
  • Output channels: 4 × DE / Class 4
  • Power modules: 1–2, hot-swap
  • Output voltage: 315–350 VDC

Managed like network equipment, not a power strip

The transmitter carries its own management interface — a 10/100 Mbps Ethernet port supporting IPv4/IPv6, a web GUI, and SNMP v1/v3 — so operations teams can monitor and manage FMP shelves the same way they manage the rest of the outside plant electronics, rather than treating power as a separate, unmonitored system.

A dry contact input lets the shelf take a signal from external equipment (such as a battery back-up system) to trigger policy actions like load shedding, and a dry contact alarm output (one normally-open, one normally-closed) reports fault conditions back to a NOC or alarm panel. Front-panel LEDs give an on-site technician an immediate read on channel and management status without opening a laptop.

Features & Benefits

Safety by design

  • Listed Class 4 system per NFPA 70 Article 726 — the circuit between transmitter and receiver disconnects on fault, including accidental contact with a conductor
  • UL 1400-1 and IEC 61508 (SIL) functional-safety listings
  • Minimum 18 AWG copper conductor requirement and a 450 Vrms minimum transmission-wiring rating keep the circuit within its designed safety margin
  • Compatible only with matched FMP receivers — the safety circuit is validated end to end, not assembled from mismatched parts

Deployment flexibility

  • Reach up to 6,000 ft on a single run, using lighter, lower-voltage-class cable than a comparable AC or DC power circuit
  • Horizontal or vertical rack mounting; power modules must sit at the bottom of the shelf in a vertical install
  • Half-power installs can be stacked with zero unit separation; full-power installs call for 1U of clearance for airflow
  • Accepts 100–250 VAC input, single-phase or bi-phase (L1/L2 or Line/Neutral), so it drops onto the power sources already available at most remote sites

Remote visibility & control

  • Web GUI and SNMP v1/v3 over a dedicated 10/100 Mbps Ethernet management port
  • Zero-config IP discovery via hostname.local, with a documented default AutoIP fallback for first-time bring-up
  • Dry contact alarm output for NOC/alarm-panel integration; dry contact input for triggering local policy such as load shedding on battery back-up
  • Per-channel fault codes (disconnected, overload, short circuit, temperature, input power, and more) reported to the front-panel LEDs and the management interface for fast field triage

Built for the outside plant

  • Operator-accessible design rated -20 °C to 50 °C, with a documented derating curve above 40 °C
  • Hot-swappable power modules keep the shelf in service during maintenance
  • Field-terminated, lever-style output connectors — no crimping or soldering required at turn-up
  • 15.25 lb, 1U chassis rated for a 30-year service life, dependent on use case

Technical Specifications

Parameter Specification Notes
Input voltage 100–250 VAC 208 VAC or greater required for full-power operation
Max current per shelf 16 A RMS per power module Minimum breaker size: 20 A per input connection
Output voltage 315–350 VDC Fault Managed Power / Class 4 output
Total power per shelf Up to 6 kW One module = 3 kW; both modules = 6 kW. Full power requires ≥208 VAC
Output channels 4
Max current per channel 4.68 A Use standard design rules for delivered power calculations
Output wiring size 18–12 AWG Copper conductors only
Max distance 6,000 ft
Recommended cable capacitance 40 pF/ft (131.2 pF/m) max Higher-capacitance cable may reduce performance
Environment & Mechanical
Parameter Specification Notes
Access location Operator accessible
Operating temperature -20 °C (-4 °F) to 50 °C (122 °F) Derate above 40 °C with 1U spacing; conditioned environment recommended
Altitude Up to 2,000 m
Humidity 20%–70%, non-condensing
Dimensions 1U; 19.20″ (487.7 mm) W × 18.67″ (474.2 mm) D × 1.75″ (44.8 mm) H Fits 19″ and 23″ racks
Weight 15.25 lbs
Safe lifetime 30 years max Dependent on use case
Communication & I/O
Parameter Specification Notes
Ethernet RJ45, 10/100 Mbps Remote monitoring and control via web GUI and SNMP v1/v3
Dry contact alarm output 1× NO, 1× NC Max steady-state current 500 mA at 25 °C
Dry contact alarm input 1× NO, 1× NC Connect to open or closed circuit only — do not apply voltage. Max cable length 3 m; 14–22 AWG; default mode open circuit
Approvals
Parameter Specification Notes
Safety UL 1400-1, UL 62368-1, EN IEC 62368-1, CAN/CSA-C22.2 No. 62368-1, IEC 61508-1/-2/-3 UL 1400-1 listed by Underwriters Laboratories
EMC FCC Part 15 Subpart B Class A, ICES-003 Class A, EN 55032 Class A, EN 300 386, EN 55035, EN 50121-4
Other CE, RoHS, WEEE, UKCA, REACH

This Website Uses Cookies

We use cookies to provide our services, to allow us to better understand our audience, and to provide and serve personalized ads or content. You can read more about our information collection in our Privacy Policy.

Close

Customize Consent Preferences

As detailed in our Privacy Policy, we use cookies or other technology that may be considered sales, sharing, or targeted advertising under certain privacy laws. You can select your preferences for optional cookies by using the checkboxes below.

These cookies are required for the operation of our sites and enable you to navigate the sites and their features.

These cookies are used to recognize you when you return to the sites and these cookies facilitate measurement and analytics for improved browsing experience.

These cookies, beacons, and pixels allow us to analyze activities on our sites. They can be used to improve the functioning of the sites. For example, these recognize and count the number of visitors and see how they move around the sites. These also help us measure the performance of and optimize the content on the site.

These cookies and pixels are used to deliver relevant ads, track ad campaign performance, or track email marketing.